Performance Characteristics and Features to look for in a UPS System

Reliability

Overall System Design

  • What is the MTBF of the system? Manufacturers should have this data.
  • Minimum single points of failure either with single module or parallel system ( Centralized Bypass is a single point of failure)

Redundancy

  • UPS should have redundant design features such as Fans, Power Supplies, Batteries, parallel communication buss.

Topology

  • Double conversion for greater load protection
  • Distributed static switches for parallel operation
  • Dual Input capable
  • Six pulse SCR or IGBT rectifier
  • Transistorized PWM or SCR inverter

Design History

  • Field proven design, large number of installs.
Installability

Standards

  • UL 1778 Listed
  • FCC Class A, Part 15 Compliant
  • IEEE 587 B Voltage Surge Withstand

EPO

  • Remote EPO capable per NEC

Foot Print

  • Minimum footprint for UPS module, battery, and options

Wiring Terminations

  • Top and bottom cable access
  • Are lugs included?

Field Retro Fit Capability

  • Can parallel UPS module be added in the field?
  • Can other options be added in the field?

Maneuverability

  • Caster and Leveling feet
Source Compatibility

Efficiency

  • 92.5 – 94% good for double conversion.

Low Input Harmonics

  • <30% THD for 6-Pulse rectifier.
  • <7% THD with optional 5th Harmonic filter.
  • <4% THD with optional 11th Harmonic filter
Input THD without filter
Input THD without filter

FCC rating

  • FCC Class A, Part 15 tested.

Building Interfaces

  • Remote EPO capable
  • External contacts for remote alarm annunciation
  • Programmable contacts
Input THD after filter
Input THD after filter

Generator Interface

  • Smart Filters available to reduce harmonics
  • Contacts available to communicate with generator
  • Adjustable parameters such as slew rate and phase angle.
Output Performance

Space Vector Modulated (PWM) inverter recommended for superior output performance.

Voltage Regulation

  • Line to Line – No more than +/-1% Vreg. for static loads
  • Line to Neutral – No more than +/-3% Vreg. for 100% load imbalance

Transient Response

  • Step Load Response – No more than +/-3% THD for steps of 0-100%
  • Recovery Time – Recovery to within +/-1% THD in less than 1 cycle

Non-Linear Capability

  • Distortion with Non-linear loads – No more than 3%THD for 100% non-linear load.

Overload Capability

  • Inverter ability – 125% for 10min, 150% for 60sec
  • Bypass ability – 110% continuous, 200% for 5min, 1000% for ½ cycle
Serviceability

Component Layout

  • Front access to main components and assemblies.
  • Internal Maintenance Bypass to reduce down time.
  • One main control board that is interchangeable with other kVA sizes, reduces parts count.

Diagnostics

  • Open Architecture, no proprietary software or hardware required for service or preventative maintenance.
  • Adjustments using parameters not potentiometers.
  • Remote diagnostics available.
  • User accessible alarm history.
  • Battery Management Software.

Parts Availability

  • 7x24 Service Center with localized parts depot.
  • Nation wide field service engineers.
Features and Options

Batteries

  • Full Line of matching battery cabinets available
  • UPS compatible with wet cell and flywheels

Software

  • Full line of monitoring, protection and management software available
  • Remote Monitoring and Diagnostic services.

Transformers

  • Full line of input and output isolation and voltage matching transformers available.

External Monitoring

  • Remote Status Panel options
  • SNMP or RS422/485 ports

Switchgear

  • External Bypass Panels, Load Static Switches, PDU’s and Automatic Transfer Switches available

 